[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022356":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022356,751,1,"单选题","某发电厂配电装置的接地装置，接地网的接地电阻计算值为0. 2020;计算用的入地短路电流采用值为9.122kA,最大接触电位差系数的计算值为0.22；最大跨步电位差系数的计算值为0.108.据此，请计算最大接触电位差和最大跨步电位差. 短路时接地装置的电位Ug是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1050V;",false,{"key":16,"text":17,"correct":18},"B","1843V；",true,{"key":20,"text":21,"correct":14},"C","2037V;",{"key":23,"text":24,"correct":14},"D","2415V。","根据DL\u002FT 621-1997P18附录B中的B2,根据计算公式计算如下UG=IR=9.122X10 3X0.202=1843（V）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]