[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022355":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022355,751,1,"单选题","在有效接地及低电阻接地系统中，校验发电厂、变电站电气装置中接地网导体截面热稳定时，不同材料（钢、铜、铝）接地网的短时温度是不同的。校验不接地、经消弧线围接地和高电阻接地系统中电气设备接地线热稳定时，敷设在地上与地下的接地线的长时间温度值也是不同的，请按下列不同情况确定接地网的短时温度。 有效接地、低电阻接地系统，钢、铜、铝材料的接地线的短时温度不大于（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","350℃、400℃、265℃；",false,{"key":16,"text":17,"correct":18},"B","400℃、450℃、300℃；",true,{"key":20,"text":21,"correct":14},"C","450℃、500℃、320℃；",{"key":23,"text":24,"correct":14},"D","500℃、550℃、350℃。","根据 DL\u002FT621—1997P7第6.2.7条规定。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]