[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022350":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022350,751,1,"单选题","某变电站的接地装置采用扁钢作接地网，接地网格为等间距布置，请根据不同的接地短路故障电流值，确定接地网的最小截面（接地材料的热稳定系数C査表为70;短路等效持续时间设为4s）。 当短路电流为12.11kA时，接地网的最小截面（取整数）为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","85mm2；",false,{"key":16,"text":17,"correct":18},"B","109mm2;",true,{"key":20,"text":21,"correct":14},"C","125mm2;",{"key":23,"text":24,"correct":14},"D","136mm2。","根据DL\u002FT 621-1997P21附录C中Cl的计算公式计算如下",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]