[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022349":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022349,751,1,"单选题","某变电站的接地装置采用扁钢作接地网，接地网格为等间距布置，请根据不同的接 地短路故障电流值，确定接地网的最小截面（接地材料的热稳定系数C査表为70;短路等效持续时间设为4s）。 当短路电流值为10. 5kA时，接地网的最小截面（取整数）为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","75mm2;",false,{"key":16,"text":17,"correct":14},"B","86mm2;",{"key":19,"text":20,"correct":21},"C","95mm2;",true,{"key":23,"text":24,"correct":14},"D","108mm2。","根据DL\u002FT 621—1997P21附录C中Cl的计算公式计算如下",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]