[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022341":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022341,751,1,"单选题","高电阻接地系统中发电厂、变电站电气装置保护接地的接地电阻计算，假定计算用接地故障电流分别为32A和45 A，请计算高压电气装置的接地电阻R。 当接地故障电流为32A时，接地电阻R应为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","R≤5.68Ω；",false,{"key":16,"text":17,"correct":14},"B","R≤6.25Ω；",{"key":19,"text":20,"correct":21},"C","R≤7.81Ω；",true,{"key":23,"text":24,"correct":14},"D","R≤8.50Ω。","根据DL\u002F1621—1997P4第5.1.1条b） 2）款计算公式计算如下",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]