[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022340":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022340,751,1,"单选题","某发电工程，在110kV与220kV发生单相接地故障时，设流经接地装置的入地短路电流I分别为12.11kA（110kV）和10.5kA（220kV），请根据入地短路电流值，按接地标准要求计算接地电阻值。 按220kV发生接地短路（10.5k A）时，接地电阻的要求值应为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.186Ω;",false,{"key":16,"text":17,"correct":18},"B","0.190Ω；",true,{"key":20,"text":21,"correct":14},"C","0.198Ω;",{"key":23,"text":24,"correct":14},"D","0.213Ω。","根据DL\u002FT 621-1997P4第5.1.1条计算公式计算如下",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]