[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022339":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022339,751,1,"单选题","某发电工程，在110kV与220kV发生单相接地故障时，设流经接地装置的入地短路电流I分别为12.11kA（110kV）和10.5kA（220kV），请根据入地短路电流值，按接地标准要求计算接地电阻值。 按110kV发生接地短路（12.11k A）时，接地电阻的要求值应为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","0.012Ω；",false,{"key":16,"text":17,"correct":14},"B","0.073Ω；",{"key":19,"text":20,"correct":14},"C","0.116Ω;",{"key":22,"text":23,"correct":24},"D","0.165Ω。",true,"根据DL\u002FT 621-1997P4第5.1.1条计算公式计算如下",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]