[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022338":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022338,751,1,"单选题","已知某35kV变电站，35kV为经消弧线圏接地系统，人脚站立处地表面的土壤电阻率ρ为100Ω?m。发生单相接地故障后，当不迅速切除故障时，此时变电站接地装置的接触电位差UT和跨步电位差Ut不应超过下列计算值。 接地装置的跨步电位差Us，不应超过的数值是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","61.5V；",false,{"key":16,"text":17,"correct":14},"B","65.3V；",{"key":19,"text":20,"correct":21},"C","70.OV；",true,{"key":23,"text":24,"correct":14},"D","74.5V。","根据DL\u002FT621-1997P3第3.4条计算公式计算如下Us=50+0.2ρf=50+0.2X100=70（V）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]