[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022337":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022337,751,1,"单选题","已知某35kV变电站，35kV为经消弧线圏接地系统，人脚站立处地表面的土壤电阻率ρ为100Ω?m。发生单相接地故障后，当不迅速切除故障时，此时变电站接地装置的接触电位差UT和跨步电位差Ut不应超过下列计算值。 接地装置的接触电位差Ut不应超过的数值是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","52.6V;",false,{"key":16,"text":17,"correct":18},"B","55.0V；",true,{"key":20,"text":21,"correct":14},"C","58.2V；",{"key":23,"text":24,"correct":14},"D","61.0V。","根据DL\u002FT621—1997P3第3.4条计算公式计算如下Ut=50+0.05ρf=50+0.05X100=55（V）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]