[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022274":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022274,751,1,"单选题","某变电所高压配电装置电压为220kV,已知所选避雷器型号是W10Y5-200\u002F496，其1OkA雷电冲击残压Ub=496kV。在主变压器与雷电过电压的绝缘配合中，确定变压器的内、外绝缘的额定雷电冲击耐受电压和内绝缘的工频耐受电压。 工频耐受电压应该不小于（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","203.7kV；",false,{"key":16,"text":17,"correct":18},"B","218.2kV；",true,{"key":20,"text":21,"correct":14},"C","232.8kV；",{"key":23,"text":24,"correct":14},"D","247.3kV。","根据DL\u002FT620—199710.4.4条的相关规定： 对220kV变压器的工频耐受电压应该不小于1.5倍系统最高相电压。即Ucz=KcUm\u002F√3=1.5X252\u002F√3=218.2(kV)",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]