[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022273":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022273,751,1,"单选题","某变电所高压配电装置电压为220kV,已知所选避雷器型号是W10Y5-200\u002F496，其1OkA雷电冲击残压Ub=496kV。在主变压器与雷电过电压的绝缘配合中，确定变压器的内、外绝缘的额定雷电冲击耐受电压和内绝缘的工频耐受电压。 额定雷电冲击耐受电压值不小于（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","545.6kV；",false,{"key":16,"text":17,"correct":14},"B","595.2kV；",{"key":19,"text":20,"correct":14},"C","644.8kV；",{"key":22,"text":23,"correct":24},"D","694.4kV。",true,"根据DL\u002FT620—199710.4.4条的相关规定： 对220kV变压器的全波额定雷电冲击耐受电压Und与避雷器残压Ubnc的配合系数Kc取1.4,即得 Und=KcUbnc=1.4X496=694.4(kV)",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]