[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022271":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022271,751,1,"单选题","已知某500kV变电所工程，550kV避雷器操作冲击残压17。为825kV，分别计算出500kV电压互感器、电流互感器的相对地和相间操作冲击耐受电压。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","相对地操作冲击耐受电压不小于（ ）。",false,{"key":16,"text":17,"correct":14},"B","907.5kV；",{"key":19,"text":20,"correct":14},"C","924.OkV； C .932.5kV；",{"key":22,"text":23,"correct":24},"D","948.8kV。",true,"根据DL\u002FT620—199710.4.3条的相关规定： 对500kV电压互感器、电流互感器的相对地操作冲击耐受电压Ucz的操作冲击配合系数Kc≥1.15。即 Und≥KcUbnc=1.15X825=948.8(kV)；",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]