[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022270":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022270,751,1,"单选题","在雷电过电压下的绝缘配合中，已知某工程选用的550kV避雷器雷电冲击残压Ubnc为1O11kV,操作冲击残压Ubcc为827kV,计算500kv电流互感器的全波額定雷电冲击耐受电压Und值和相对地操作冲击耐受电压Ucz值。 相对地操作冲击耐受电压值是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","951kV；",true,{"key":16,"text":17,"correct":18},"B","976kV；",false,{"key":20,"text":21,"correct":18},"C","992kV；",{"key":23,"text":24,"correct":18},"D","1034kV。","根据DL\u002FT620—199710.4.3条、10.4.4条的相关规定： 对500kV电流互感器相对地操作冲击耐受电压U3的操作冲击配合系数Kc取1.15.即 Ucz=KcUbcc=1.15X827=951(kV)。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]