[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022269":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022269,751,1,"单选题","在雷电过电压下的绝缘配合中，已知某工程选用的550kV避雷器雷电冲击残压Ubnc为1O11kV,操作冲击残压Ubcc为827kV,计算500kv电流互感器的全波額定雷电冲击耐受电压Und值和相对地操作冲击耐受电压Ucz值。 全波额定雷电冲击耐受电压Und值是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1213kV；",false,{"key":16,"text":17,"correct":14},"B","1314kV；",{"key":19,"text":20,"correct":21},"C","1415kV；",true,{"key":23,"text":24,"correct":14},"D","1516kV。","根据DL\u002FT620—199710.4.3条、10.4.4条的相关规定： 对500kV电流互感器的全波额定雷电冲击耐受电压Und与避雷器残压Ubnc的配合系数Kc取1.4，即得 Und=KcUbnc=1.4X1011=1415(kV),",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]