[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022268":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022268,751,1,"单选题","单机容量为12000kW的直配电机，在少雷区除按采用标准保护接线外，对于1OkV线路，在进线保护段长度L0内，应装设避雷针（线）。当排气式避雷器的接地电阻R分别是和60时，确定进线保护段长度L0应该满足的要求。 当R=6时，L0应该满足的要求是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","L0≥750m；",false,{"key":16,"text":17,"correct":14},"B","L0≥780m；",{"key":19,"text":20,"correct":14},"C","L0≥825m；",{"key":22,"text":23,"correct":24},"D","L0≥900m.",true,"根据DL\u002FT620—19979.5条的相关规定和公式（22)L0≥150R,分别代入R的数据即得： L0≥150R=150X6=900(m)。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]