[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022250":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022250,751,1,"单选题","某发电厂采用三回110kV架空出线，且全线均有避雷线。11OkV配电装置采用双母线接线，每组母线上装设了金属氧化锌避雷器。请按此条件分析确定应在主变压器附近增设一组避雷器的避雷器与主变压器的电气距离。 当采用五回110kV架空出线时，避雷器与主变压器的最大电气距离是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","210m；",false,{"key":16,"text":17,"correct":18},"B","230m;",true,{"key":20,"text":21,"correct":14},"C","235m;",{"key":23,"text":24,"correct":14},"D","265m。","根据DL\u002FT620—19977.2査表12的相关数据即可确定： 当采用五回11OkV架空出线时，避雷器与主变压器的最大电气距离是230m。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]