[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022169":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022169,751,1,"单选题","某500kV变电所，变压器侧避雷器的额定电压为420kV，20kA标称雷电流下的额定残压值为995kV;线路断路器侧避雷器的额定电压为444kV,20kA标称雷电流下的额定残压值为1050kV。 变压器截波雷电冲击耐压最小值为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1523kV；",false,{"key":16,"text":17,"correct":18},"B","1532kV；",true,{"key":20,"text":21,"correct":14},"C","1537kV；",{"key":23,"text":24,"correct":14},"D","1541kV。","根据DL\u002FT620~199710.4.4条的相关规定，变压器内绝缘全波雷电冲击耐压最小值为： 在变压器截波雷电冲击耐压取其全波額定雷电冲击耐压最小值的1.1倍，即：1.1Und=1.1X1393=1532(kV)。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]