[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022168":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022168,751,1,"单选题","某500kV变电所，变压器侧避雷器的额定电压为420kV，20kA标称雷电流下的额定残压值为995kV;线路断路器侧避雷器的额定电压为444kV,20kA标称雷电流下的额定残压值为1050kV。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","其他电气设备内绝缘全波额定雷电冲击耐压最小值为（）。",false,{"key":16,"text":17,"correct":14},"B","1461kV；",{"key":19,"text":20,"correct":21},"C","1466kV；",true,{"key":23,"text":24,"correct":14},"D","1470kV； a1475kV。","根据DL\u002FT620~199710.4.4条的相关规定，变压器内绝缘全波雷电冲击耐压最小值为： 对其他电气设备内绝缘全波额定雷电冲击耐压Und与避雷器残压Ubnc的配合系数Kc≥l.4，即得变压器内绝缘全波雷电冲击耐压最小值为 Und=KcUbnc=1.4X1050=1470(kV)。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]