[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022134":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022134,751,1,"单选题","对范围II的线路，若系统送受端联系薄弱，将产生线路非对称故障分闸或振荡解列过电压。如预测该过电压趄过2.2p.u.（330kV）、2.Op.u.（500kV），宜采取的限制措施是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","线路受端安装金属氧化物避雷器；",false,{"key":16,"text":17,"correct":14},"B","线路送端安装金属氧化物避雷器；",{"key":19,"text":20,"correct":21},"C","线路送、受端同时安装金属氣化物避雷器；",true,{"key":23,"text":24,"correct":14},"D","线路中间安装金属氧化物避雷器。","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]