[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022131":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022131,751,1,"单选题","选择并校验1OOMW发电机一变压器组的连接母线.已知：发电机额定电压为10.5kV,额定电流为6468A,最大负荷利用小时数为5200h,发电机连接母线上短路电流为I\"=35.4kA,\u002F00=22.8KPa。地区最热月平均温度为+35℃,发电机连接母线三相水平布置。 应进行的校验不包括（ ）。 选用标准槽型铝母线200X90X12 (hXbXt), S=8080mm2,按环境温度+35℃ 的综合校正后的载流量为（）》",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","7744A；",true,{"key":16,"text":17,"correct":18},"B","8272A；",false,{"key":20,"text":21,"correct":18},"C","7128A；",{"key":23,"text":24,"correct":18},"D","8800A。","查DL\u002FT 5222—2005附录D表D:11、表D.10，综合校正系数为0.88,载流量为8800A。按环境温度+35℃的综合校正后的载流量为8800X0.88=7744(A)。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]