[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022117":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022117,751,1,"单选题","选择并校验1OOMW发电机一变压器组的连接母线.已知：发电机额定电压为10.5kV,额定电流为6468A,最大负荷利用小时数为5200h,发电机连接母线上短路电流为I\"=35.4kA,\u002F00=22.8KPa。地区最热月平均温度为+35℃,发电机连接母线三相水平布置。 宜选用的母线型式为（ ）.",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","矩形；",false,{"key":16,"text":17,"correct":14},"B","管形；",{"key":19,"text":20,"correct":21},"C","槽形；",true,{"key":23,"text":24,"correct":14},"D","软导线。","根据DL\u002FT 5222—2005第7.3.2条，电流为4000~8000A时，宜选用槽形导体。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]