[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022116":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022116,751,1,"单选题","某发电厂髙压厂用变压器型号和参数如下：SFFPL—31500\u002F15、31500\u002F16000-16000kV A、15.75±2X2.5\u002F6.3—6.3kV;短路时通过6.3kV侧母线的冲击电流为ich=55.8kA,6kV母线选用2XLMY—100X10母线，母线安装为竖放，环境温度按40℃考虑。 选用2 XLMY — 100X10母线，在40℃环境温度及母线自振频率（ )(绝缘子间跨距为100cm).",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","173.6Hz;",false,{"key":16,"text":17,"correct":18},"B","180.5Hz;",true,{"key":20,"text":21,"correct":14},"C","135.5Hz；",{"key":23,"text":24,"correct":14},"D","200Hz。","根据《电力工程电气设计手册》(1)第8-1节第二条第（四）款公式8-27及表8-13,母线自振频率为",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]