[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022073":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022073,751,1,"单选题","某工程，500kV母线穿越功率为2500MW, 500kV母线短路参数：I\"=27.19kA,I∞=24.22kA,71.24k A，短路热效应Q=95.6kA2s;计算时间：t=0.1\",环境最髙温度为+29.7℃,海拔髙度为400m,500kV母线选用2XLGJQT—1400。 校验电晕电压值应（ ）550kV。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","小于；",false,{"key":16,"text":17,"correct":18},"B","大于；",true,{"key":20,"text":21,"correct":14},"C","等于；",{"key":23,"text":24,"correct":14},"D","不大于。","根据DL\u002FT5222—2005第7.1.7条，校验电晕电压值应大于550kV。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]