[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021966":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1021966,751,1,"单选题","发电厂主变压器容量及台数选择。 发电厂主变压器绕组的数量，下面所述错误的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","最大机组容量为125MW及以下的发电厂以两种升高电压向用户供电或与电力系统连接时，其主变压器宜采用三绕组变压器；",false,{"key":16,"text":17,"correct":18},"B","对于机组容量在200MW及以上的发电厂，当有两种升高电压等级时，宜采用三绕组变压器；",true,{"key":20,"text":21,"correct":14},"C","机组容量在200MW及以上的发电厂，一般都采用与双绕组变压器组成单元接线；",{"key":23,"text":24,"correct":14},"D","当机组容量在200MW及以上时，一般都采用与双绕组变压器组成单元接线，而不与三绕组变压器组成单元接线，当发电机具有两种升髙电压等级时，則装设联络变压器。","根据 DL5000—2000第13.1.7条。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]