[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021963":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1021963,751,1,"单选题","有一中型凝汽式火电厂，装机容量为2X1OOMW+2X55MW，发电机出口电压为10.5kV,发电机电压出线10回，10回的最大综合负荷为80MW,最小为40MW,110kV出线共4回，每回输送容量相同。 11OkV采用双母线，其母联断路器的额定电流应选择（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1000A；",false,{"key":16,"text":17,"correct":18},"B","1600A；",true,{"key":20,"text":21,"correct":14},"C","2000A；",{"key":23,"text":24,"correct":14},"D","2500A。","根据《电力工程电气设计手册》（l）第6~1节表6-3母联回路的计算电流为1个最大电源元件的计算电流，对11OkV母线，最大电源元件为主变压器，其计算电流为1.05X240\u002F（√3X121）=1202（A）。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]