[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021961":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1021961,751,1,"单选题","有一中型凝汽式火电厂，装机容量为2X1OOMW+2X55MW，发电机出口电压为10.5kV,发电机电压出线10回，10回的最大综合负荷为80MW,最小为40MW,110kV出线共4回，每回输送容量相同。 对主变压器的选择，正确的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1台330MVA的双绕组变压器；",false,{"key":16,"text":17,"correct":14},"B","2台170MVA的双绕组变压器；",{"key":19,"text":20,"correct":14},"C","2台200MVA的双绕组变压器；",{"key":22,"text":23,"correct":24},"D","2台240MVA的双绕组变压器。",true,"说明：100MW发电机的功率因数为0.85，55MW发电机的功率因数为0.8，IOkV负荷的功率因数一般为0.8，可算出送入11OkV的容量应为2X100\u002F0.85+2X55\u002F0.8-40\u002F0.8=323（MVA），按规程应设置2台主变压器，每台主变压器不小于70%。 每台主变压器不小于70%、323MVAX0.7=226（MVA）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]