[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021959":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1021959,751,1,"单选题","隔离开关的设置与功能。 关于隔离开关的设置正确的有（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","330~500kV避雷器和线路电压互感器均应装设隔离开关；",false,{"key":16,"text":17,"correct":14},"B","中小型发电机出口一般可不装设隔离开关；",{"key":19,"text":20,"correct":14},"C","220kV及以下线路避雷器和接在发电机与变压器引出线的避雷器均应装设隔离开关；",{"key":22,"text":23,"correct":24},"D","在出线装设电抗器的6~10kv配电装置中，当向不同用户供电的两回线共用一台断路器和一组电抗器时，每回线上应各装设一组出线隔离开关。",true,"根据《火力发电厂设计技术规程》（DL 5000-2000）第13.2.6条和《电力工程电气设计手册》（1）第2-8节第一条之规定，只有在出线装设电抗器的6~IOkV配电装置中，当向不同用户供电的两回线共用一台断路器和一组电抗器时，每回线上应各装设一组出线隔离开关。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]