[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021954":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1021954,751,1,"单选题","某发电厂发电机装机容量为2x 50MW，功率因数cosψ=0.85，额定电压为10.5kV，接线均为发电机，变压器组接上11OkV升压站，发电机回路和升压变压器绕组及1OkV导体的电容电流为11A。 3~66kV电网采用中性点不接地方式，但当电网架空线路单相接地故障电流最小大于（）又需在接地故障条件下运行时，主变压器中性点应经消弧线圈接地。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","40A；",false,{"key":16,"text":17,"correct":14},"B","30A；",{"key":19,"text":20,"correct":14},"C","20A；",{"key":22,"text":23,"correct":24},"D","10A。",true,"根据《交流电气装置的过电压保护和绝缘配合》（DL\u002FT620-1997）第3.1.2条规定，当电网架空线路单相接地故障电流最小大于1OA又需在接地故障条件下运行时，主变压器中性点应经消弧线圈接地。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]