[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021939":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1021939,751,1,"单选题","某电厂装机容量为25MW，发电机出口电压为6.3kV,cosψ=0.8。 发电机出口装设电流互感器应选用的型号规范为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","LMZD2—10\u002F1500,一次额定电流为1500A；",false,{"key":16,"text":17,"correct":14},"B","LMZD2—10\u002F2000,一次额定电流为2000A；",{"key":19,"text":20,"correct":14},"C","LMZD2—10\u002F3000,一次颏定电流为3000A；",{"key":22,"text":23,"correct":24},"D","LMZD2—10\u002F4000,一次额定电流为4000A。",true,"根据《电力工程电气设计手册》（1）第6-5节第一条第（三）款，计算如下： 发电机的额定电流为 用于测量的电流互感器一次额定电流比回路正常工作电流大1\u002F3,应为2863X1.333=3817（A）,取4000A,故发电机出口电流互感器的型号规范为LMZD2—10\u002F4000，一次额定电流为4000A。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]