[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021934":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1021934,751,1,"单选题","某工程6kV配电装置其出线带电抗器。 6kV出线系厂用电源，最大一台厂用辅机（给水泵）电动机型号为YK2000—2\u002F1180,额定功率Pe=2000kW，启动电流倍数kg=6，功率因素cosψ=0.86，效率η=O.95，给水果电动机启动前已带负荷S1=4576kV A，应选用的电抗器为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","XKK-6-800-5；",false,{"key":16,"text":17,"correct":14},"B","XKK—6—1000-5；",{"key":19,"text":20,"correct":14},"C","XKK-6-1500-5；",{"key":22,"text":23,"correct":24},"D","XKK-6-2000-5。",true,"根据《火力发电厂厂用电设计技术规定KDL\u002FT5153—2002）第5.4.1条，最大容量电动机正常起动时厂用母线电压不应低于额定电压的80%,现选用XKK-6-如00-5型电抗器，正常起动时厂用母线电压为",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]