[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021933":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1021933,751,1,"单选题","某工程6kV配电装置其出线带电抗器。 6kV出线回路电压损失为3.15%,为满足线路末端电压损失不大于5%，应选用电抗器的型号规范为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","XKK-6-600-5；",false,{"key":16,"text":17,"correct":14},"B","XKK—6—80.0-5；",{"key":19,"text":20,"correct":21},"C","XKK—6-1000-5；",true,{"key":23,"text":24,"correct":14},"D","XKK-6-1500-5。","电抗器上的允许电压损失为5%—3.15%=1.85%，选用XKK-6-1000-5型电抗器， 取Sinψ=0.6，则电坑器上的电压损失为 线路末端电压损失为Σ△u%=3.15%+1.569%≈4.72% 5%。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]