[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021929":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1021929,751,1,"单选题","某热电厂扩建2台机组，发电机单机额定容量Se=50MW,额定功率因数为0.85,额定电压Ue=10.5kV，2台发电机以扩大单元接线接入已建的11OkV升压站。经计算，发电机电压回路及主变压器低压绕组的电容电流总计为4.5A。 主变压器宜选择（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","2台60MVA的变压器；",false,{"key":16,"text":17,"correct":14},"B","1台120MVA的双绕组变压器；",{"key":19,"text":20,"correct":21},"C","1台120\u002F60—60MVA的低压分裂绕组变压器；",true,{"key":23,"text":24,"correct":14},"D","1台120MVA的三绕组变压器。","根据《电力工程电气设计手册》（l）第5-1节第一条之规定，采用扩大单元接线时，主变压器应选用分裂绕组变压器，其容量按两台发电机的额定容量扣除厂用电（按10%估算）并考虑的10%裕度或按发电机最大连续输出容量（假设为55MW）扣除厂用电计算，二者取其大者。按前者计算，则主变压器容量为1.1X2X50X（1-0.1）\u002F0.85=116.47（MVA）,按后者计算，则主变压器容量为2X55X（1-0.1）\u002F0.85=116.47（MVA）。所以，本热电厂主变压器宜选用1台120\u002F60—60MVA的低压分裂绕组变压器。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]