[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021928":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1021928,751,1,"单选题","某发电厂装机为2X350MW+2X200MW，以发电机一变压器组单元接线接入220kV配电装置，送出线路共5回，每回线路的最大输送功率均为300MW,功率因素cosψ=0.85。主变压器为420MVA或250MV A，髙压侧抽头为（230—2X2.5%）kV。220kV配电装置选用双母线单分段出线带旁路母线接线。 该电厂2台350MW机组和2台200MW机组的发电机额定电压可以分别是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","20kV,18kV；",false,{"key":16,"text":17,"correct":14},"B","22kV,20kV；",{"key":19,"text":20,"correct":14},"C","22kV,18kV；",{"key":22,"text":23,"correct":24},"D","18kV,15.75kV.",true,"解答过程： 按《电力工程电气设计手册》（1） P232表6-3。 根据《透平型同步电机技术要求》（GB\u002FT 7064—2002）表5规定，300MW发电机的额定电压为18kV或20kV，200MW发电机的额定电压为15.75kV，故该电厂2台350MW机组和2台200MW机组的发电机额定电压可以分别是18kV,15.75kV。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]