[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021926":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1021926,751,1,"单选题","—台电压比为525\u002F230±8X1.25%\u002F35kV的自耦变压器，当高压側电压升髙到550kV时，要求中压侧仍维持230kV. 调压后，低压侧电压为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","35kV；",false,{"key":16,"text":17,"correct":14},"B","37.5kV；",{"key":19,"text":20,"correct":21},"C","37.9kV；",true,{"key":23,"text":24,"correct":14},"D","38.2kV。","解答过程： 计算过程参考《电力工程电气设计手册》（1）第219页。 分接头的位置应放到6X1.25%位置上，这样实际调整减少的匝数 △W=2.88X6=17.28（匝）。再重新核算调整后中压侧的实际电压为 每匝电动势为 第三绕组电压U3=35X1.083=37.905（kV）。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]