[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021925":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1021925,751,1,"单选题","—台电压比为525\u002F230±8X1.25%\u002F35kV的自耦变压器，当高压側电压升髙到550kV时，要求中压侧仍维持230kV. 分接头位置应选择（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","5；",false,{"key":16,"text":17,"correct":18},"B","6；",true,{"key":20,"text":21,"correct":14},"C","7；",{"key":23,"text":24,"correct":14},"D","8。","计算过程参考《电力工程电气设计手册》（1）第219页。 B 设W1,W2、W3分别为高、中、低绕组匝数，△W为需调整的匝数， 则W1：W2：W3=U1：U2：U3=525：230：35 即可假定W1=525匝，W2=230匝，W3=35匝 调整前后的中压侧电压应维持不变，其调整后的匝数比和电压比为 1.39△W=2.39 W2-W1=549.7-525=24.7 △W=17.77（匝） 每挡抽头调整电压为1.25%，则相应变化的匝数为 230X1.25%=2.88匝 调整△W匝数，需调抽头档数为17.77\u002F2.88=6.17≈6",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]