[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021920":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1021920,751,1,"单选题","某热电厂装机2X50MW, cosΨ=0.8,接10.5kV发电机电压母线，10.5kV为双母线单分段接线，为限制短路电流，分段回路装设有限流电抗器。 发电机电压负荷最大为70MW，最小为45MW,cosψ=0.8,为将剩余容量送入系统，需装设主变压器，下列装设方式最合理的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1台70MVA的变压器；",false,{"key":16,"text":17,"correct":14},"B","2台70MVA的变压器；",{"key":19,"text":20,"correct":21},"C","2台50MVA的变压器；",true,{"key":23,"text":24,"correct":14},"D","2台40MVA的变压器。","根据《电力工程电气设计手册》（1）第5-1节第一条，应选2台主变压器，每台能送出剩余容量的70%。剩余容量为（2X50—45）\u002F0.8=69（MVA）,69X0.7=48.3（MVA）,故应选2台50MVA的变压器.",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]