[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021916":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1021916,751,1,"单选题","某发电厂升压站220kV配电装置的主接线为四角形接线，2台200MW发电机组,2回出线。 如果短路水平按40k A，TA准确级取5P20\u002F5P20\u002F5P20\u002F0.5\u002F0.2，则四角形内TA变比宜为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","2000-4000\u002F5A；",false,{"key":16,"text":17,"correct":14},"B","1500-3000\u002F5A；",{"key":19,"text":20,"correct":21},"C","1000-2000\u002F5A；",true,{"key":23,"text":24,"correct":14},"D","800-1600\u002F5A。","40000\u002F20=2000A,故变比宜为1000—2000\u002F5A。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]