[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021874":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":21,"analysis":22},1021874,751,1,"单选题","某11OkV变电站，主变压器电压为110\u002F35\u002F10kV，容量为40MV A，无功；用并联电容器装置装设于1OkV侧，假定并联电容器补偿容量按主变容量的10%装设，分成两组，电网主谐波为5次及以上，3次谐波不超标，请分析（或计算）回答以下问题。 当单台电容器容量为1OOkvar,选择外熔断器作单台电容器内部故障保护时，熔断器的熔丝额定电流为（）。",[11,15,18],{"key":12,"text":13,"correct":14},"A","18A；",false,{"key":16,"text":17,"correct":14},"B","20A； C22A；",{"key":19,"text":20,"correct":14},"C","24","","根据《高压并联电容器单台电容器保护用熔断器订货技术条件》（DL 442—1991）附录A熔丝额定电流的配置推荐值，表Al电容器的额定电压应为11\u002F√3kV,电容器的额定容量为1OOkvar,对应的熔丝额定电流为24A。",{"id":6,"name":24,"category":25,"favorite":26},"电气工程师发输变电专业","建筑工程",0]