[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021873":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1021873,751,1,"单选题","某11OkV变电站，主变压器电压为110\u002F35\u002F10kV，容量为40MV A，无功；用并联电容器装置装设于1OkV侧，假定并联电容器补偿容量按主变容量的10%装设，分成两组，电网主谐波为5次及以上，3次谐波不超标，请分析（或计算）回答以下问题。 针对本题情况，选择适合本站电容器组的接线和保护方式（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","双星形接线采用中性点不平衡电流保护;",false,{"key":16,"text":17,"correct":14},"B","单星形接线采用相电压差动保；",{"key":19,"text":20,"correct":21},"C","单星形接线采用开口三角电压保护；",true,{"key":23,"text":24,"correct":14},"D","单星形接线采用桥式差电流保护。","根据GB 50227—1995第6.1.2条的相关规定，电容器组接线和保护方式共有4种方式，2000kvar为小型电容器组，1OkV通常为单串联段。A.电容器组应能分成两个星形，适合容量较大的电容器组；B.适合于每相为两个及以上的串联段的电容器组；C.电容器组的每相要能构成4个桥臂，电压为1OkV的小容量电容器组一般不采用这种方式。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]