[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021865":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1021865,751,1,"单选题","某11OkV系统，断路器的全分闸时间为0.06s，主保护动作时间为0.09s，后备保护动作时间为1.94s。 仍采用上述热效应，确定110kV铜管母线最小热稳定截面为（）（短路前导体温度为50℃）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","175mm2；",true,{"key":16,"text":17,"correct":18},"B","185mm2；",false,{"key":20,"text":21,"correct":18},"C","330mm2；",{"key":23,"text":24,"correct":18},"D","365mm2.","根据《电力工程电气浙手册》⑴第S-I节第二条第（四）款的相美规定，按短路前温度C50-C）确定铜导体发热系数C=181，铜管母线最小热稳定截面",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]