[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021811":3},{"question":4,"library":22},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":15,"analysis":21},1021811,751,1,"单选题","220kV线路（见图5-15）K点发生相间短路，电源、线路阻抗标么值已在图中注明，额定电压为220kV，基准容量为1000MVA。 图5-16中K点相间短路时复合序网图正确的是（ ）。",[11,14,17,19],{"key":12,"text":12,"correct":13},"A",false,{"key":15,"text":15,"correct":16},"B",true,{"key":18,"text":18,"correct":13},"C",{"key":20,"text":20,"correct":13},"D","根据《导体和电器选择设计技术规定》（DL\u002FT5222—2005）附录F.5.2的（F.5.2-1）式确定：两相短路时，短路点的正序短路电流的合成阻抗（标么值）为正序和负序合成阻抗之和。据此可判定，在四个复合序网图中，只有图B是正确的。",{"id":6,"name":23,"category":24,"favorite":25},"电气工程师发输变电专业","建筑工程",0]