[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021793":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1021793,751,1,"单选题","某电厂现有装机为2台300MW机组，规划容量为4X300MW机组，每台机组均采用发电机一变压器組单元接线接入厂内220kV母线.已知：220kV系统电抗为0.2（Sj=1OOOMV A）；主变压器370MVA,Ud=14%；发电机Xd'=16%,cosψ=0.85，出口电压为20kV,根据每台机的计算电抗Xjs,査运算曲线，可知每台机的短路电流标么值为3.7，当220kV母线发生三相短路时： 发电机的电抗标么值是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.476；",false,{"key":16,"text":17,"correct":18},"B","0.453；",true,{"key":20,"text":21,"correct":14},"C","0.557；",{"key":23,"text":24,"correct":14},"D","0.53。","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]