[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021787":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":22},1021787,751,1,"单选题","某电厂现有装机为4台300MW机组，每台机组均采用发电机一变庄器组单元接线接入厂内220kV母线。已知220kV母线发生三相短路时各电源提供的短路电流周期分量有效值为I\"=26k A，冲击系数Kch=1.85。 冲击电流Ich是（ ）。 A.36.8kA;",[11,15,18],{"key":12,"text":13,"correct":14},"A","48.1kA；",false,{"key":16,"text":17,"correct":14},"B","68.02kA；",{"key":19,"text":20,"correct":21},"C","83.3k",true,"",{"id":6,"name":24,"category":25,"favorite":26},"电气工程师发输变电专业","建筑工程",0]