[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1021786":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1021786,751,1,"单选题","某电厂现有装机为4台300MW机组，每台机组均采用发电机一变庄器组单元接线接入厂内220kV母线。已知220kV母线发生三相短路时各电源提供的短路电流周期分量有效值为I\"=26k A，冲击系数Kch=1.85。 短路容量S”是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","9907.3MVA；",false,{"key":16,"text":17,"correct":18},"B","10357.7MVA；",true,{"key":20,"text":21,"correct":14},"C","5720MVA；",{"key":23,"text":24,"correct":14},"D","5980MVA。","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]