[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1012989":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1012989,739,1,"单选题","TN系统中在工作接地以外，在专用保护线PE上一处或多出再次与接地装置相连称为重复接地。当系统中发生碰壳或接地短路时．可降低零线的对地电压，当零线发生断裂时，可使故障程度减轻。下列关于重复接地的要求中，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","TN系统中的保护零线必须在配电室或总配电箱处做重复接地外",false,{"key":16,"text":17,"correct":14},"B","TN系统中的保护零线必须在配电系统的末端处做重复接地",{"key":19,"text":20,"correct":21},"C","TN系统中的保护零线在配电室或总配电箱处和配电系统的末端处已做重复接地，可不在配电系统的中间处做重复接地",true,{"key":23,"text":24,"correct":14},"D","在TN系统中，保护零线每一处重复接地装置的接地电阻值不应大于10Ω","TN系统中的保护零线除必须在配电室或总配电箱处做重复接地外，还必须在配电系统的中间处和末端处做重复接地。",{"id":6,"name":27,"category":28,"favorite":29},"安全实务-建筑施工安全","建筑工程",0]