[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1012953":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1012953,739,1,"单选题","下列开关箱和总配电箱(配电柜)内配置漏电保护器的漏电动作参数说法中，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","开关箱中的漏电保护器，一般场所其额定漏电动作电流为不大于30mA，额定漏电动作时间为不大于0.1s",false,{"key":16,"text":17,"correct":14},"B","Ⅰ类和Ⅱ类（非塑料外壳）手持电动工具其额定漏电动作电流为不大于15mA，额定漏电动作时间不大于0.1s",{"key":19,"text":20,"correct":14},"C","施工降水、夯实、振捣、地面抹光（水磨石）、水泵供水场所其额定漏电动作电流为不大于15mA，额定漏电动做时间不大于0.1s",{"key":22,"text":23,"correct":24},"D","总配电箱中的漏电保护器，其额定漏电动作电流为不大于30mA，额定漏电动作时间应不大于0.1s，其额定漏电动做电流与额定漏电动作时间的乘积不超过安全界限值30mA&middot;s",true,"总配电箱中的漏电保护器，其额定漏电动作电流为大于30 mA，额定漏电动作时间应大于0.1s，但其额定漏电动做电流与额定漏电动作时间的乘积不超过安全界限值30 mA?s。",{"id":6,"name":27,"category":28,"favorite":29},"安全实务-建筑施工安全","建筑工程",0]