[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-996453":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},996453,729,2,"多选题","漏电保护是为了保证安全而安装的装置，下列系统中发生设备外壳漏电的时候，漏电保护可能会动作的是（）",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","IT 系统",false,{"key":16,"text":17,"correct":18},"B","TT 系统",true,{"key":20,"text":21,"correct":14},"C","TN-C 系统",{"key":23,"text":24,"correct":18},"D","TN-C-S 系统",{"key":26,"text":27,"correct":18},"E","TN-S 系统","BDE","剩余电流动作保护装置用于间接接触电击事故防护时，应正确地与电网的系统接地型式相配合。在TN 系统中，必须将TN—C 系统改造为TN—C—S、TN—S 系统或局部TT 系统后，才可安装使用剩余电流动作保护装置。在TN—C—S 系统中，剩余电流动作保护装置只允许用在N 线与PE 线分开部分。",{"id":6,"name":31,"category":32,"favorite":33},"安全生产技术基础","建筑工程",0]