[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-995388":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},995388,729,1,"单选题","对地电压指带电体与零电位大地之间的电位差。下图所示为TT系统[即配电变压器低压中性点（N点）直接接地，用电设备（M）的外壳也直接接地的系统]示意图。已知低压中性点接地电阻R N =2Ω、设备外壳接地电阻R M =3Ω、配电线路相电压U=220V。当用电设备发生金属性漏电（即接触电阻接近于零）时，该设备对地电压为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","200V",false,{"key":16,"text":17,"correct":18},"B","132V",true,{"key":20,"text":21,"correct":14},"C","88V",{"key":23,"text":24,"correct":14},"D","110V","当用电设备发生金属性漏电时，即计算设备对大地的电压差，也就是将施加在人体上的电压。设备外壳接地与配电变压器线路形成回路，总电阻为中性点接地电阻和设备外壳接地电阻之和，通过已知计算漏电流后，算出对地电压，即为该设备的对地电压。本题计算方法为：①漏电流220V÷（2Ω+3Ω）＝44A，②对地电压44A×3Ω＝132V。",{"id":6,"name":27,"category":28,"favorite":29},"安全生产技术基础","建筑工程",0]