[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-704-34":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":533},{"id":5,"name":6,"category":7,"favorite":8},704,"中级技能","建筑工程",0,34,50,2486,[13,38,48,54,60,66,80,92,104,116,128,140,151,157,163,169,175,181,192,198,204,216,231,242,248,260,275,287,298,304,310,316,331,343,349,362,374,380,392,404,418,433,447,462,477,488,494,504,516,522],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":36,"analysis":37},974599,2,"多选题","下列关于防烟排烟系统送风口、排烟口保养要求的说法正确的是（ ）。",[19,23,26,29,32],{"key":20,"text":21,"correct":22},"A","排烟口、送风口无变形、损伤",true,{"key":24,"text":25,"correct":22},"B","固定牢靠，与建筑墙体、吊顶贴合紧密，风口内无杂物和积尘",{"key":27,"text":28,"correct":22},"C","旋转机构灵活，无卡滞和阻碍",{"key":30,"text":31,"correct":22},"D","制动机构、限位器符合要求",{"key":33,"text":34,"correct":35},"E","手动、自动、远程启闭操作正常",false,"ABCD","",{"id":39,"libraryId":5,"type":40,"typeLabel":41,"stem":42,"options":43,"answer":45,"analysis":37},974600,3,"判断题","火灾时，为防止灭火时的消防积水淹没消防电梯导致消防电梯失去功能，消防电梯的井底应设置排水设施。",[44,46],{"key":20,"text":45,"correct":22},"正确",{"key":24,"text":47,"correct":35},"错误",{"id":49,"libraryId":5,"type":40,"typeLabel":41,"stem":50,"options":51,"answer":47,"analysis":37},974601,"在消防控制室点机与指定的消防电话分机、电话插孔之间互相呼叫与通话。",[52,53],{"key":20,"text":45,"correct":35},{"key":24,"text":47,"correct":22},{"id":55,"libraryId":5,"type":40,"typeLabel":41,"stem":56,"options":57,"answer":47,"analysis":37},974602,"消防设备末端配电装置的清扫和检修一般每月至少一次，其内容除清扫和摇测绝缘外，还应检查各部连接点和接地处的紧固状况。",[58,59],{"key":20,"text":45,"correct":35},{"key":24,"text":47,"correct":22},{"id":61,"libraryId":5,"type":40,"typeLabel":41,"stem":62,"options":63,"answer":45,"analysis":37},974603,"断路器开关动作试验：动作灵活，开关的指示位置与实际位置一致，储能机构动作正常，开关的电动、手动操作正常，电气、机械联锁正常可靠。",[64,65],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":67,"libraryId":5,"type":68,"typeLabel":69,"stem":70,"options":71,"answer":30,"analysis":37},974604,1,"单选题","下列关于消防设备末端配电装置操作按钮的保养要求说法错误的是（ ）。",[72,74,76,78],{"key":20,"text":73,"correct":35},"设备外观应清洁干净",{"key":24,"text":75,"correct":35},"所有接线应紧固，无破损及烧焦现象",{"key":27,"text":77,"correct":35},"接点、触头表面应清洁，无氧化层，接触紧密，分合可靠",{"key":30,"text":79,"correct":22},"绝缘电阻不大于1MΩ",{"id":81,"libraryId":5,"type":68,"typeLabel":69,"stem":82,"options":83,"answer":30,"analysis":37},974605,"消防设备末端配电装置的清扫和检修一般（ ），其内容除清扫和摇测绝缘外，还应检查各部连接点和接地处的紧固状况。",[84,86,88,90],{"key":20,"text":85,"correct":35},"每月至少一次",{"key":24,"text":87,"correct":35},"每季至少一次",{"key":27,"text":89,"correct":35},"每半年至少一次",{"key":30,"text":91,"correct":22},"每年至少一次",{"id":93,"libraryId":5,"type":68,"typeLabel":69,"stem":94,"options":95,"answer":24,"analysis":37},974606,"下列关于消防电话系统保养不属于功能检查项目的是（ ）。",[96,98,100,102],{"key":20,"text":97,"correct":35},"通话功能",{"key":24,"text":99,"correct":22},"报警功能",{"key":27,"text":101,"correct":35},"显示功能",{"key":30,"text":103,"correct":35},"总机群呼、录音功能",{"id":105,"libraryId":5,"type":68,"typeLabel":69,"stem":106,"options":107,"answer":24,"analysis":37},974607,"下列关于消防应急广播设备功能检查中，对应急广播声压级的保养要求说法正确的是（ ）。",[108,110,112,114],{"key":20,"text":109,"correct":35},"距扬声器正前方3m处，用数字声级计测量应急广播声压级（A权计）不应小于65d B，且不应大于120dB",{"key":24,"text":111,"correct":22},"在环境噪声大于60dB的场所设置的扬声器，在其播放范围内最远点的播放声压级应高于背景噪声15dB",{"key":27,"text":113,"correct":35},"距扬声器正前方5m处，用数字声级计测量应急广播声压级（A权计）不应小于65d且不应大于115dB",{"key":30,"text":115,"correct":35},"在环境噪声大于60dB的场所设置的扬声器，在其播放范围内最远点的播放声压级应高于背景噪声20dB",{"id":117,"libraryId":5,"type":68,"typeLabel":69,"stem":118,"options":119,"answer":20,"analysis":37},974608,"消防电梯的井底应设置排水设施。排水井的容量和排水泵的排水量分别不应小于（ ）。",[120,122,124,126],{"key":20,"text":121,"correct":22},"2m3；10L\u002Fs",{"key":24,"text":123,"correct":35},"10m3；2L\u002Fs",{"key":27,"text":125,"correct":35},"5m3；10L\u002Fs",{"key":30,"text":127,"correct":35},"10m3；5L\u002Fs",{"id":129,"libraryId":5,"type":68,"typeLabel":69,"stem":130,"options":131,"answer":24,"analysis":37},974609,"下列关于消防电梯挡水、排水设施电气控制柜的保养要求说法错误的是（ ）。",[132,134,136,138],{"key":20,"text":133,"correct":35},"外观完好，仪表、指示灯正常，开关、按钮运转灵活、无卡滞",{"key":24,"text":135,"correct":22},"供电正常",{"key":27,"text":137,"correct":35},"控制柜内清洁，无积灰、杂物",{"key":30,"text":139,"correct":35},"电气连接紧密，无松动",{"id":141,"libraryId":5,"type":68,"typeLabel":69,"stem":142,"options":143,"answer":27,"analysis":37},974610,"下列关于应急照明控制器保养功能检查项目不包括（ ）。",[144,146,148,149],{"key":20,"text":145,"correct":35},"自检功能",{"key":24,"text":147,"correct":35},"消音、故障报警功能",{"key":27,"text":101,"correct":22},{"key":30,"text":150,"correct":35},"主备电源的自动转换功能",{"id":152,"libraryId":5,"type":40,"typeLabel":41,"stem":153,"options":154,"answer":47,"analysis":37},974611,"排水井的容量不应小于5m3，排水泵的排水量不应小于10L\u002Fs。消防电梯间前室的门口宜设置挡水设施。",[155,156],{"key":20,"text":45,"correct":35},{"key":24,"text":47,"correct":22},{"id":158,"libraryId":5,"type":40,"typeLabel":41,"stem":159,"options":160,"answer":45,"analysis":37},974612,"对电气元器件的清洁应使用吸尘器或软毛刷等工具，其他组件可使用不太湿的布进行擦拭。对损坏件应及时维修或更换。",[161,162],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":164,"libraryId":5,"type":40,"typeLabel":41,"stem":165,"options":166,"answer":45,"analysis":37},974613,"电气控制柜进行外观检查和功能测试，根据检查情况分别进行清洁、清理、紧固和维修(对电气部件清洁应使用吸尘器或软毛刷)。",[167,168],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":170,"libraryId":5,"type":40,"typeLabel":41,"stem":171,"options":172,"answer":47,"analysis":37},974614,"应急广播声压级测试在距扬声器正前方3m处，用数字声级计测量应急广播声压级(A权计)不应小于70dB，且不应大于115dB。",[173,174],{"key":20,"text":45,"correct":35},{"key":24,"text":47,"correct":22},{"id":176,"libraryId":5,"type":40,"typeLabel":41,"stem":177,"options":178,"answer":45,"analysis":37},974615,"电气火灾监控器保养工作完成后，应将设备恢复到正常工作状态。（ ）",[179,180],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":182,"libraryId":5,"type":68,"typeLabel":69,"stem":183,"options":184,"answer":27,"analysis":37},974616,"防烟排烟系统的风管的保养要求，不包含（ ）。",[185,187,189,190],{"key":20,"text":186,"correct":35},"风管无变形损坏",{"key":24,"text":188,"correct":35},"风管吊架支撑牢固，在各种工况下均无晃动",{"key":27,"text":21,"correct":22},{"key":30,"text":191,"correct":35},"风管穿墙处防火封堵完好",{"id":193,"libraryId":5,"type":40,"typeLabel":41,"stem":194,"options":195,"answer":45,"analysis":37},974617,"明杆闸阀的润滑作业的保养程序，如下图。",[196,197],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":199,"libraryId":5,"type":40,"typeLabel":41,"stem":200,"options":201,"answer":45,"analysis":37},974618,"消防设备末端配电装置保养操作时，用湿布清洁装置外壳表面，去除污渍、灰尘，并保证指示灯、显示屏清晰可见。（ ）",[202,203],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":205,"libraryId":5,"type":68,"typeLabel":69,"stem":206,"options":207,"answer":30,"analysis":37},974619,"不属于气压罐及供水附件保养要求的是（ ）。",[208,210,212,214],{"key":20,"text":209,"correct":35},"组件齐全，固定牢靠",{"key":24,"text":211,"correct":35},"外观无损伤、锈蚀",{"key":27,"text":213,"correct":35},"压力表当前指示正常，稳压泵启停压力设定正确，联动启动消防主泵功能正常",{"key":30,"text":215,"correct":22},"出水水量符合要求",{"id":217,"libraryId":5,"type":15,"typeLabel":16,"stem":218,"options":219,"answer":230,"analysis":37},974620,"保养湿式自动喷水灭火系统的阀门时，保养方法正确的是（ ）。",[220,222,224,226,228],{"key":20,"text":221,"correct":22},"发现铅封损坏的，及时更换铅封",{"key":24,"text":223,"correct":35},"发现阀门启闭不灵活的，可以不处理",{"key":27,"text":225,"correct":22},"发现锁链未固定在规定状态的，调整锁链至规定的固定状态",{"key":30,"text":227,"correct":22},"发现阀门有漏水、诱蚀等情形的，更换阀门密封垫，修理或者更换阀门，对锈蚀部位进行除锈处理",{"key":33,"text":229,"correct":22},"发现阀门启闭不灵活的，进行润滑处理","ACDE",{"id":232,"libraryId":5,"type":68,"typeLabel":69,"stem":233,"options":234,"answer":30,"analysis":37},974621,"消防设备末端配电装置的母线保养要求不包含（ ）。",[235,236,238,240],{"key":20,"text":73,"correct":35},{"key":24,"text":237,"correct":35},"表面应清洁平整，无毛刺和氧化层，接触应紧密可靠，螺栓应紧固",{"key":27,"text":239,"correct":35},"相间及相对地绝缘电阻不低于1MΩ",{"key":30,"text":241,"correct":22},"机构应灵活可靠",{"id":243,"libraryId":5,"type":40,"typeLabel":41,"stem":244,"options":245,"answer":45,"analysis":37},974622,"消防设备末端配电装置的清扫和检修一般每年至少一次。（ ）",[246,247],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":249,"libraryId":5,"type":68,"typeLabel":69,"stem":250,"options":251,"answer":24,"analysis":37},974623,"应急照明控制器的保养项目不包含（ ）。",[252,254,256,258],{"key":20,"text":253,"correct":35},"外观检查",{"key":24,"text":255,"correct":22},"安全性检査",{"key":27,"text":257,"correct":35},"接线检查",{"key":30,"text":259,"correct":35},"功能检查",{"id":261,"libraryId":5,"type":15,"typeLabel":16,"stem":262,"options":263,"answer":274,"analysis":37},974624,"线型感烟、感温火灾探测器的保养操作需要准备的纸质资料包含（ ）。",[264,266,268,270,272],{"key":20,"text":265,"correct":22},"消防工程竣工图纸",{"key":24,"text":267,"correct":35},"清洁的干软布",{"key":27,"text":269,"correct":35},"螺丝刀",{"key":30,"text":271,"correct":22},"《建筑消防设施维护保养记录表》",{"key":33,"text":273,"correct":35},"酒精","AD",{"id":276,"libraryId":5,"type":68,"typeLabel":69,"stem":277,"options":278,"answer":30,"analysis":37},974625,"探测器功能检查的保养要求是（ ）。",[279,281,283,285],{"key":20,"text":280,"correct":35},"产品标识应清晰、明显",{"key":24,"text":282,"correct":35},"接线端子应无松动",{"key":27,"text":284,"correct":35},"底座与墙体应稳定",{"key":30,"text":286,"correct":22},"报警功能测试",{"id":288,"libraryId":5,"type":68,"typeLabel":69,"stem":289,"options":290,"answer":27,"analysis":37},974626,"消防电话系统保养操作程序的最后一个步骤是（ ）。",[291,293,295,297],{"key":20,"text":292,"correct":35},"接通消防电话总机电源，使消防电话处于正常监视状态",{"key":24,"text":294,"correct":35},"保养完成后，对消防电话总机进行复位和自检操作，等待2min，观察消防电话主机是否处于正常监视状态",{"key":27,"text":296,"correct":22},"填写《建筑消防设施维护保养记录表》",{"key":30,"text":259,"correct":35},{"id":299,"libraryId":5,"type":40,"typeLabel":41,"stem":300,"options":301,"answer":45,"analysis":37},974627,"电气火灾监控器的显示屏有显示不正常的问题应及时修复。（ ）",[302,303],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":305,"libraryId":5,"type":40,"typeLabel":41,"stem":306,"options":307,"answer":47,"analysis":37},974628,"消防应急广播系统的保养操作完成后，只需对消防应急广播系统进行复位即可。（ ）",[308,309],{"key":20,"text":45,"correct":35},{"key":24,"text":47,"correct":22},{"id":311,"libraryId":5,"type":40,"typeLabel":41,"stem":312,"options":313,"answer":45,"analysis":37},974629,"防烟排烟系统的风机保养要求之一是铭牌清晰。（ ）",[314,315],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":317,"libraryId":5,"type":15,"typeLabel":16,"stem":318,"options":319,"answer":330,"analysis":37},974630,"关于消防设备末端配电装置的保养方法，正确的有（ ）。",[320,322,324,326,328],{"key":20,"text":321,"correct":22},"配电装置断电后，用电动吹风或小毛刷等清洁柜中灰尘",{"key":24,"text":323,"correct":22},"检查断路器操作机构是否到位，接线螺栓是否紧固",{"key":27,"text":325,"correct":35},"如接触器触点磨损至原厚度的2\u002F3，应更换触点",{"key":30,"text":327,"correct":22},"检查电源指示仪表、指示灯应完好",{"key":33,"text":329,"correct":22},"清洁消防设备末端配电装置前应停电","ABDE",{"id":332,"libraryId":5,"type":68,"typeLabel":69,"stem":333,"options":334,"answer":30,"analysis":37},974631,"消防应急广播系统的保养操作步骤分别为：①接通电源，使消防应急广播设备系统、火灾自动报警系统设备处于正常工作状态②外观检查保养③接线检查保养④功能检查⑤填写《建筑消防设施维护保养记录表》⑥保养完成后，对消防应急广播系统进行复位和自检操作。正确的操作顺序是（ ）。",[335,337,339,341],{"key":20,"text":336,"correct":35},"①②③④⑤⑥",{"key":24,"text":338,"correct":35},"⑥①②③④⑤",{"key":27,"text":340,"correct":35},"①③④⑤②⑥",{"key":30,"text":342,"correct":22},"①②③④⑥⑤",{"id":344,"libraryId":5,"type":40,"typeLabel":41,"stem":345,"options":346,"answer":45,"analysis":37},974632,"对干式自动喷水灭火系统中的水流指示器的保养要求是：外观完好，标识明显，水流指示器的启动与复位灵敏、可靠，反馈信号准确。（ ）",[347,348],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":350,"libraryId":5,"type":15,"typeLabel":16,"stem":351,"options":352,"answer":361,"analysis":37},974633,"可燃气体报警控制器的开关、按键保养要求为（ ）。",[353,355,357,358,359],{"key":20,"text":354,"correct":22},"孔隙清洁",{"key":24,"text":356,"correct":35},"指示灯应清晰可见",{"key":27,"text":280,"correct":35},{"key":30,"text":282,"correct":35},{"key":33,"text":360,"correct":22},"功能标注清楚可读","AE",{"id":363,"libraryId":5,"type":68,"typeLabel":69,"stem":364,"options":365,"answer":30,"analysis":37},974634,"消防电梯排水设施保养时，要求排水井的容量不应小于（ ）m3。",[366,368,370,372],{"key":20,"text":367,"correct":35},"1",{"key":24,"text":369,"correct":35},"5",{"key":27,"text":371,"correct":35},"10",{"key":30,"text":373,"correct":22},"2",{"id":375,"libraryId":5,"type":40,"typeLabel":41,"stem":376,"options":377,"answer":47,"analysis":37},974635,"防（排）烟风机保养操作时，应连续运转1~3min,验证风机运转正常。（ ）",[378,379],{"key":20,"text":45,"correct":35},{"key":24,"text":47,"correct":22},{"id":381,"libraryId":5,"type":68,"typeLabel":69,"stem":382,"options":383,"answer":27,"analysis":37},974636,"对泵组的保养要求，不正确的是（ ）。",[384,386,388,390],{"key":20,"text":385,"correct":35},"组件齐全，泵体和电动机外壳完好，无破损、锈蚀",{"key":24,"text":387,"correct":35},"设备铭牌标志清晰",{"key":27,"text":389,"correct":22},"叶轮转动灵活，可以有轻微卡滞",{"key":30,"text":391,"correct":35},"润滑油充足，泵体、泵轴无渗水、砂眼",{"id":393,"libraryId":5,"type":68,"typeLabel":69,"stem":394,"options":395,"answer":20,"analysis":37},974637,"对湿式自动喷水灭火系统的报警阀组保养时，保养方法不正确的是（ ）。",[396,398,400,402],{"key":20,"text":397,"correct":22},"检查阀瓣上的橡胶密封垫，表面不清洁，可以不清洗",{"key":24,"text":399,"correct":35},"检查阀座的环形槽和小孔，发现积存泥沙和污物时进行清洗",{"key":27,"text":401,"correct":35},"阀座密封面应平整，无碰伤和压痕，否则应修理或更换",{"key":30,"text":403,"correct":35},"检查阀瓣上的橡胶密封垫，表面有损伤，应更换",{"id":405,"libraryId":5,"type":15,"typeLabel":16,"stem":406,"options":407,"answer":230,"analysis":37},974638,"关于总线控制盘的工作原理，下列说法正确的是（ ）",[408,410,412,414,416],{"key":20,"text":409,"correct":22},"火灾报警控制系统主要采用总线控制盘，其信号线由两根线组成，信号与供电共用一个总线",{"key":24,"text":411,"correct":35},"总线控制盘的每一个按键对应一个或多个总线控制模块，对消防设备的控制是由控制模块实现",{"key":27,"text":413,"correct":22},"总线控制盘具有对每个受控消防设备进行手动控制的功能",{"key":30,"text":415,"correct":22},"一台集中火灾报警控制器（联动型）可以设置多个总线控制盘",{"key":33,"text":417,"correct":22},"消防联动控制器可通过操作总线控制盘的按键、控制模块手动控制消防设备的动作",{"id":419,"libraryId":5,"type":15,"typeLabel":16,"stem":420,"options":421,"answer":432,"analysis":37},974639,"电气火灾监控器接线保养的保养方法包含（ ）。",[422,424,426,428,430],{"key":20,"text":423,"correct":22},"检查接线端子有无松动情况，发现松动应用螺丝刀紧固，确保连接紧密",{"key":24,"text":425,"correct":35},"用小毛刷将孔隙里的灰尘和杂质清扫岀来，再用吸尘器清理干净",{"key":27,"text":427,"correct":22},"检査线路接头处有无氧化或锈蚀痕迹，若有则应采取防潮、防锈措施",{"key":30,"text":429,"correct":35},"应该用干燥的抹布擦拭干净表面污渍",{"key":33,"text":431,"correct":22},"发现螺栓、垫片及配件有生锈现象应及时予以更换","ACE",{"id":434,"libraryId":5,"type":15,"typeLabel":16,"stem":435,"options":436,"answer":432,"analysis":37},974640,"检查消防泵房的防淹措施时，主要看（ ）。",[437,439,441,443,445],{"key":20,"text":438,"correct":22},"挡水门槛",{"key":24,"text":440,"correct":35},"消防水池高度",{"key":27,"text":442,"correct":22},"排水沟",{"key":30,"text":444,"correct":35},"泵房供电情况",{"key":33,"text":446,"correct":22},"集水坑",{"id":448,"libraryId":5,"type":15,"typeLabel":16,"stem":449,"options":450,"answer":461,"analysis":37},974641,"消防电梯的排水设施保养项目包括（ ）。",[451,453,455,457,459],{"key":20,"text":452,"correct":22},"排水井",{"key":24,"text":454,"correct":22},"排水泵",{"key":27,"text":456,"correct":22},"电气控制柜",{"key":30,"text":458,"correct":35},"挡水设施外观",{"key":33,"text":460,"correct":35},"消防电梯","ABC",{"id":463,"libraryId":5,"type":15,"typeLabel":16,"stem":464,"options":465,"answer":476,"analysis":37},974642,"在保养电气火灾监控器时，检查线路接头处有氧化或锈蚀痕迹，则应采取防潮、防锈措施有（ ）。",[466,468,470,472,474],{"key":20,"text":467,"correct":35},"重新连接接头",{"key":24,"text":469,"correct":22},"镀锡",{"key":27,"text":471,"correct":35},"用水冲洗干净",{"key":30,"text":473,"correct":22},"涂抹凡士林",{"key":33,"text":475,"correct":35},"用普通纸张包裹","BD",{"id":478,"libraryId":5,"type":68,"typeLabel":69,"stem":479,"options":480,"answer":27,"analysis":37},974643,"保养气压罐及供水附件时，对管道泄压，发现稳压泵自动启停和消防水泵启动压力设定不正确的，应对（ ）进行调整、维修或更换。",[481,483,485,487],{"key":20,"text":482,"correct":35},"水流指示器",{"key":24,"text":484,"correct":35},"水箱的水位传感器",{"key":27,"text":486,"correct":22},"压力开关",{"key":30,"text":456,"correct":35},{"id":489,"libraryId":5,"type":40,"typeLabel":41,"stem":490,"options":491,"answer":45,"analysis":37},974644,"保养消防控制室图形显示装置的显示屏表面时，应用湿布擦拭清洁干净。（ ）",[492,493],{"key":20,"text":45,"correct":22},{"key":24,"text":47,"correct":35},{"id":495,"libraryId":5,"type":68,"typeLabel":69,"stem":496,"options":497,"answer":24,"analysis":37},974645,"没有报脏功能的线型感烟探测器，应按产品说明书的要求进行清洁保养；产品说明书没有明确要求的，应每（ ）年清洁或标定一次。",[498,499,500,502],{"key":20,"text":367,"correct":35},{"key":24,"text":373,"correct":22},{"key":27,"text":501,"correct":35},"3",{"key":30,"text":503,"correct":35},"4",{"id":505,"libraryId":5,"type":68,"typeLabel":69,"stem":506,"options":507,"answer":24,"analysis":37},974646,"水力警铃检查的保养方法，不包括（ ）。",[508,510,512,514],{"key":20,"text":509,"correct":35},"清洗报警管路上的过滤器",{"key":24,"text":511,"correct":22},"增加水压",{"key":27,"text":513,"correct":35},"拆下铃壳，彻底清除脏物和泥沙并重新安装",{"key":30,"text":515,"correct":35},"拆下水轮上的漏水接头，清洁其中集聚的污物",{"id":517,"libraryId":5,"type":40,"typeLabel":41,"stem":518,"options":519,"answer":47,"analysis":37},974647,"使用螺丝刀调整机械式压力开关的两个调节螺钉的调整方式为精确调整。（ ）",[520,521],{"key":20,"text":45,"correct":35},{"key":24,"text":47,"correct":22},{"id":523,"libraryId":5,"type":68,"typeLabel":69,"stem":524,"options":525,"answer":27,"analysis":37},974648,"消防控制室内集中火灾报警控制器、消防联动控制器、消防控制室图形显示装置及火灾显示盘的保养操作程序中第一步是（ ）。",[526,528,530,532],{"key":20,"text":527,"correct":35},"用小毛刷将机柜（壳）内设备空隙和线材上的灰尘和杂质清扫出来，然后用吸尘器清理干净",{"key":24,"text":529,"correct":35},"保养结束后，给控制器送电，用钥匙将箱门锁闭",{"key":27,"text":531,"correct":22},"使用钥匙打开箱门，将控制器主、备电源切断",{"key":30,"text":296,"correct":35},[534,537,540,543,546,549],{"id":68,"name":535,"category":7,"favorite":536},"领导干部任职前廉政法规知识测试题",92,{"id":538,"name":539,"category":7,"favorite":68},595,"建筑结构与设备",{"id":541,"name":542,"category":7,"favorite":68},715,"招标采购专业知识与法律法规",{"id":544,"name":545,"category":7,"favorite":68},848,"市政方向-通用基础",{"id":547,"name":548,"category":7,"favorite":8},534,"BIM工程师",{"id":550,"name":548,"category":7,"favorite":8},535]