[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-704-26":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":500},{"id":5,"name":6,"category":7,"favorite":8},704,"中级技能","建筑工程",0,26,50,2486,[13,38,53,68,83,98,108,114,120,126,132,138,144,150,156,162,168,174,180,186,192,198,204,210,216,230,236,242,248,256,268,280,292,304,312,324,336,348,356,368,380,392,400,408,416,428,443,457,471,486],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":36,"analysis":37},974195,2,"多选题","线型光束感烟火灾探测器的设置应符合下列规定：（ ）。",[19,23,26,29,33],{"key":20,"text":21,"correct":22},"A","探测器的光束轴线至顶棚的垂直距离宜为0.3m～1.0m",true,{"key":24,"text":25,"correct":22},"B","相邻两组探测器的水平距离不应大于14m",{"key":27,"text":28,"correct":22},"C","探测器至侧墙水平距离不应大于7m，且不应小于0.5m",{"key":30,"text":31,"correct":32},"D","探测器的发射器和接收器之间的距离不宜超过10m",false,{"key":34,"text":35,"correct":32},"E","探测器距地高度不宜超过16m","ABC","",{"id":39,"libraryId":5,"type":15,"typeLabel":16,"stem":40,"options":41,"answer":52,"analysis":37},974196,"线型感温火灾探测器的设置应符合下列规定：（ ）。",[42,44,46,48,50],{"key":20,"text":43,"correct":22},"设置在顶棚下方的线型感温火灾探测器，至顶棚的距离宜为0.1m",{"key":24,"text":45,"correct":32},"探测器至墙壁的距离宜为1m～1.2m",{"key":27,"text":47,"correct":22},"光栖光纤感温火灾探测器每个光栅的保护面积和保护半径，应符合点型感温火灾探测器的保护面积和保护半径要求",{"key":30,"text":49,"correct":32},"设置线型感温火灾探测器的场所有联动要求时，宜采用两只不同类型的火灾探测器的报警信号组合",{"key":34,"text":51,"correct":22},"与线型感温火灾探测器连接的模块不宜设置在长期潮湿或温度变化较大的场所","ACE",{"id":54,"libraryId":5,"type":15,"typeLabel":16,"stem":55,"options":56,"answer":67,"analysis":37},974197,"下列关于火灾显示盘的设置要求说法正确的有（ ）。",[57,59,61,63,65],{"key":20,"text":58,"correct":22},"每个报警区域设置一台火灾显示盘",{"key":24,"text":60,"correct":32},"当采用壁挂方式安装时，火灾显示盘底边距地高度为1.2m",{"key":27,"text":62,"correct":22},"当一个报警区域包括多个楼层时，在每个楼层设置一台仅显示本楼层的火灾显示盘",{"key":30,"text":64,"correct":22},"火灾显示盘应设置在出入口等明显和便于操作的部位",{"key":34,"text":66,"correct":22},"当采用壁挂方式安装时，火灾显示盘底边距地高度为1.5m","ACDE",{"id":69,"libraryId":5,"type":15,"typeLabel":16,"stem":70,"options":71,"answer":82,"analysis":37},974198,"下列属于火灾显示盘应具有的功能有（ ）。",[72,74,76,78,80],{"key":20,"text":73,"correct":22},"火灾报警显示",{"key":24,"text":75,"correct":22},"故障显示",{"key":27,"text":77,"correct":22},"自检",{"key":30,"text":79,"correct":22},"信息显示与查询",{"key":34,"text":81,"correct":22},"电源","ABCDE",{"id":84,"libraryId":5,"type":15,"typeLabel":16,"stem":85,"options":86,"answer":97,"analysis":37},974199,"下列关于火灾显示盘功能描述正确的有（ ）。",[87,89,91,93,95],{"key":20,"text":88,"correct":22},"火灾显示盘应能在火灾报警控制器发出火灾报警信号后3s内发出火灾报警声、光信号",{"key":24,"text":90,"correct":22},"火灾显示盘，应在火灾报警控制器发出故障信号后3s内发出故障声、光信号",{"key":27,"text":92,"correct":32},"火灾显示盘应具有自动检查其音响器件、面板上所有指示灯和显示器等工作状态的功能",{"key":30,"text":94,"correct":32},"主电源应能保证火灾显示盘在火灾报警状态下连续工作8h，且应有过流保护措施",{"key":34,"text":96,"correct":22},"采用主电源为220V、50Hz交流电源供电的火灾显示盘应具有主电源和备用电源转换功能","ABE",{"id":99,"libraryId":5,"type":100,"typeLabel":101,"stem":102,"options":103,"answer":107,"analysis":37},974200,3,"判断题","火灾报警控制器处于“手动、自动”任意的状态下，都能发出手动启动命令。",[104,106],{"key":20,"text":105,"correct":32},"正确",{"key":24,"text":107,"correct":22},"错误",{"id":109,"libraryId":5,"type":100,"typeLabel":101,"stem":110,"options":111,"answer":105,"analysis":37},974201,"点击“报警历史记录查询”，可查询火警、监管、反馈及是否消除、启动及是否停止、故障及是否恢复、屏蔽及是否解除、其他事件。",[112,113],{"key":20,"text":105,"correct":22},{"key":24,"text":107,"correct":32},{"id":115,"libraryId":5,"type":100,"typeLabel":101,"stem":116,"options":117,"answer":107,"analysis":37},974202,"消防联动控制器在自动控制状态下，插入手动操作，不能控制受控消防设备的启动或停止。",[118,119],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":121,"libraryId":5,"type":100,"typeLabel":101,"stem":122,"options":123,"answer":105,"analysis":37},974203,"间接控制是指控制信号通过消防电气控制装置间接作用到连接的消防电动装置，进而实现对受控消防设备的控制。",[124,125],{"key":20,"text":105,"correct":22},{"key":24,"text":107,"correct":32},{"id":127,"libraryId":5,"type":100,"typeLabel":101,"stem":128,"options":129,"answer":105,"analysis":37},974204,"直线控制一般采用多线控制，即采用独立的手动控制单元，每个控制单元通过直接连接的导线和控制模块对应控制一个受控消防设备，属于点对点控制方式。",[130,131],{"key":20,"text":105,"correct":22},{"key":24,"text":107,"correct":32},{"id":133,"libraryId":5,"type":100,"typeLabel":101,"stem":134,"options":135,"answer":107,"analysis":37},974205,"总线控制盘的每一个按键对应一个总线控制模块，对消防设备的控制是由手动按钮控制实现的。",[136,137],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":139,"libraryId":5,"type":100,"typeLabel":101,"stem":140,"options":141,"answer":107,"analysis":37},974206,"多线控制盘的操作按钮与消防泵组（喷淋泵组、消火栓泵组）、防烟和排烟风机的控制柜控制按钮直接用控制线或控制电缆连接，实现对现场设备的自动控制。",[142,143],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":145,"libraryId":5,"type":100,"typeLabel":101,"stem":146,"options":147,"answer":105,"analysis":37},974207,"多线制控制盘也称作多线制手动控制盘或直接手动控制盘。",[148,149],{"key":20,"text":105,"correct":22},{"key":24,"text":107,"correct":32},{"id":151,"libraryId":5,"type":100,"typeLabel":101,"stem":152,"options":153,"answer":105,"analysis":37},974208,"为确保操作受控消防设备的可靠性，对于一些重要联动设备（如消防泵组、防烟和排烟风机）的控制，除采用联动控制方式外，火灾报警控制器还应采用多线控制盘控制方式，实现直接手动控制。",[154,155],{"key":20,"text":105,"correct":22},{"key":24,"text":107,"correct":32},{"id":157,"libraryId":5,"type":100,"typeLabel":101,"stem":158,"options":159,"answer":107,"analysis":37},974209,"多线控制盘与火灾报警控制器连接，一台火灾报警控制器（联动型）应设置一个多线控制盘。",[160,161],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":163,"libraryId":5,"type":100,"typeLabel":101,"stem":164,"options":165,"answer":107,"analysis":37},974210,"多线控制盘每个操作按钮对应两个控制输出，控制喷淋泵组、消火栓泵组、防烟和排烟风机等消防设备的启动，可根据需要按下目标操作按钮启动对应的消防设备。",[166,167],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":169,"libraryId":5,"type":100,"typeLabel":101,"stem":170,"options":171,"answer":107,"analysis":37},974211,"线型定温火灾探测器的选择，应保证其不动作温度符合设置场所的最低环境温度的要求。",[172,173],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":175,"libraryId":5,"type":100,"typeLabel":101,"stem":176,"options":177,"answer":107,"analysis":37},974212,"在正常情况下有烟滞留的场所，宜选择线型光束感烟火灾探测器。",[178,179],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":181,"libraryId":5,"type":100,"typeLabel":101,"stem":182,"options":183,"answer":107,"analysis":37},974213,"线型定温火灾探测器的选择，应保证其动作温度符合设置场所的最高环境温度的要求。",[184,185],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":187,"libraryId":5,"type":100,"typeLabel":101,"stem":188,"options":189,"answer":107,"analysis":37},974214,"设置在顶棚下方的线型感温火灾探测器，至顶棚的距离宜为0.5m。探测器的保护半径应符合点型感温火灾探测器的保护半径要求；探测器至墙壁的距离宜为1m-1.5m。",[190,191],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":193,"libraryId":5,"type":100,"typeLabel":101,"stem":194,"options":195,"answer":107,"analysis":37},974215,"按动作性能可分为可恢复式和不可恢复式线型感温探测器。",[196,197],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":199,"libraryId":5,"type":100,"typeLabel":101,"stem":200,"options":201,"answer":107,"analysis":37},974216,"按定位方式可分为探测型和探测报警型线型感温火灾探测器。",[202,203],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":205,"libraryId":5,"type":100,"typeLabel":101,"stem":206,"options":207,"answer":107,"analysis":37},974217,"在距离终端盒0.3m以外的部位，使用温度不低于54℃的热水持续对线型缆式感温火灾探测器的感温电缆进行加热，线型感温火灾探测器应在10s以内发出火灾报警信号，探测器红色报警确认灯点亮，火灾报警控制器显示火警信号。",[208,209],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":211,"libraryId":5,"type":100,"typeLabel":101,"stem":212,"options":213,"answer":105,"analysis":37},974218,"选择减光值为0.4dB的滤光片。将滤光片置于线型光束感烟火灾探测器的光路中并尽可能靠近接收器。30S内火灾报警器应发出火警信号，探测器报警确认灯点亮。",[214,215],{"key":20,"text":105,"correct":22},{"key":24,"text":107,"correct":32},{"id":217,"libraryId":5,"type":218,"typeLabel":219,"stem":220,"options":221,"answer":20,"analysis":37},974219,1,"单选题","在火灾报警控制器上，按下（ ）可消除火灾报警控制器发出的火警或故障警报声。",[222,224,226,228],{"key":20,"text":223,"correct":22},"消音键",{"key":24,"text":225,"correct":32},"复位键",{"key":27,"text":227,"correct":32},"自检键",{"key":30,"text":229,"correct":32},"取消键",{"id":231,"libraryId":5,"type":100,"typeLabel":101,"stem":232,"options":233,"answer":107,"analysis":37},974220,"选择减光值为11.5dB的滤光片。将滤光片置于线型光束感烟火灾探测器的发射器与接收器之间，并尽可能靠近接收器的光路上。线型光束感烟火灾探测器应发出火灾报警。",[234,235],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":237,"libraryId":5,"type":100,"typeLabel":101,"stem":238,"options":239,"answer":107,"analysis":37},974221,"火灾显示盘应设置在出入口等明显和便于操作的部位。当采用壁挂方式安装时，其底边距地高度宜为1.5m～1.8m。",[240,241],{"key":20,"text":105,"correct":32},{"key":24,"text":107,"correct":22},{"id":243,"libraryId":5,"type":100,"typeLabel":101,"stem":244,"options":245,"answer":105,"analysis":37},974222,"当一个报警区域包括多个楼层时，宜在每个楼层设置一台仅显示本楼层的火灾显示盘。",[246,247],{"key":20,"text":105,"correct":22},{"key":24,"text":107,"correct":32},{"id":249,"libraryId":5,"type":218,"typeLabel":219,"stem":250,"options":251,"answer":24,"analysis":37},974223,"在火灾报警控制器上，按下（ ）可使火灾自动报警系统或系统内各组成部分恢复到正常监视状态。",[252,253,254,255],{"key":20,"text":223,"correct":32},{"key":24,"text":225,"correct":22},{"key":27,"text":227,"correct":32},{"key":30,"text":229,"correct":32},{"id":257,"libraryId":5,"type":218,"typeLabel":219,"stem":258,"options":259,"answer":20,"analysis":37},974224,"当火灾报警控制器中的联动逻辑关系满足时，且控制器处于“（ ）”的状态下，控制器会发出自动联动启动命令，并接收反馈动作信号。",[260,262,264,266],{"key":20,"text":261,"correct":22},"自动允许",{"key":24,"text":263,"correct":32},"手动",{"key":27,"text":265,"correct":32},"部分自动",{"key":30,"text":267,"correct":32},"不允许",{"id":269,"libraryId":5,"type":218,"typeLabel":219,"stem":270,"options":271,"answer":27,"analysis":37},974225,"下列复位操作不可能实现的功能是：（ ）",[272,274,276,278],{"key":20,"text":273,"correct":32},"清除消音状态",{"key":24,"text":275,"correct":32},"清除正处于请求和延时请求启动命令",{"key":27,"text":277,"correct":22},"清除故障",{"key":30,"text":279,"correct":32},"清除总线制手动控制盘上的状态指示灯",{"id":281,"libraryId":5,"type":218,"typeLabel":219,"stem":282,"options":283,"answer":27,"analysis":37},974226,"下列不属于设备信息查看分类的是（ ）。",[284,286,288,290],{"key":20,"text":285,"correct":32},"设备查看",{"key":24,"text":287,"correct":32},"分类查看",{"key":27,"text":289,"correct":22},"分层查看",{"key":30,"text":291,"correct":32},"分区查看",{"id":293,"libraryId":5,"type":218,"typeLabel":219,"stem":294,"options":295,"answer":20,"analysis":37},974227,"点击一个有负载的回路，出现回路配接设备的位图信息。在位图显示方式下，“T”表示（ ）。",[296,298,300,302],{"key":20,"text":297,"correct":22},"报警类型",{"key":24,"text":299,"correct":32},"手动按钮",{"key":27,"text":301,"correct":32},"消火栓按钮",{"key":30,"text":303,"correct":32},"压力开关",{"id":305,"libraryId":5,"type":218,"typeLabel":219,"stem":306,"options":307,"answer":27,"analysis":37},974228,"点击一个有负载的回路，出现回路配接设备的位图信息。在位图显示方式下，“X”表示（ ）。",[308,309,310,311],{"key":20,"text":297,"correct":32},{"key":24,"text":299,"correct":32},{"key":27,"text":301,"correct":22},{"key":30,"text":303,"correct":32},{"id":313,"libraryId":5,"type":218,"typeLabel":219,"stem":314,"options":315,"answer":20,"analysis":37},974229,"点击切换键，回路配接设备位图显示切换为列表显示，列表显示可以方便地查看每一个地址的详细信息。下列关于第一列的表示说法正确的是（ ）。",[316,318,320,322],{"key":20,"text":317,"correct":22},"第一列为回路-地址以及设备所在的X和Y分区",{"key":24,"text":319,"correct":32},"第一列为描述信息和楼层位置等信息",{"key":27,"text":321,"correct":32},"第一列为设备类型以及对应的盘号键值",{"key":30,"text":323,"correct":32},"第一列为当前状态",{"id":325,"libraryId":5,"type":218,"typeLabel":219,"stem":326,"options":327,"answer":30,"analysis":37},974230,"在图形显示装置（CRT）中，查询历史记录可通过“（ ）”菜单实现。",[328,330,332,334],{"key":20,"text":329,"correct":32},"维保记录",{"key":24,"text":331,"correct":32},"设备信息",{"key":27,"text":333,"correct":32},"备份数据库",{"key":30,"text":335,"correct":22},"日志查询",{"id":337,"libraryId":5,"type":218,"typeLabel":219,"stem":338,"options":339,"answer":27,"analysis":37},974231,"如果（ ）指示灯处于闪烁状态，表示总线控制盘手动控制单元已发出启动指令，等待反馈。",[340,342,344,346],{"key":20,"text":341,"correct":32},"“允许”",{"key":24,"text":343,"correct":32},"“禁止”",{"key":27,"text":345,"correct":22},"\"启动”",{"key":30,"text":347,"correct":32},"“反馈”",{"id":349,"libraryId":5,"type":218,"typeLabel":219,"stem":350,"options":351,"answer":30,"analysis":37},974232,"如果（ ）指示灯处于熄灭状态，表示现场设备启动信息没有反馈回来。",[352,353,354,355],{"key":20,"text":341,"correct":32},{"key":24,"text":343,"correct":32},{"key":27,"text":345,"correct":32},{"key":30,"text":347,"correct":22},{"id":357,"libraryId":5,"type":218,"typeLabel":219,"stem":358,"options":359,"answer":27,"analysis":37},974233,"多线控制盘（ ），控制喷淋泵组、消火栓泵组、防烟和排烟风机等消防设备的启动，可根据需要按下目标操作按钮启动对应的消防设备。",[360,362,364,366],{"key":20,"text":361,"correct":32},"每两个操作按钮对应一个控制输出",{"key":24,"text":363,"correct":32},"每个操作按钮对应两个控制输出",{"key":27,"text":365,"correct":22},"每个操作按钮对应一个控制输出",{"key":30,"text":367,"correct":32},"每两个操作按钮对应两个控制输出",{"id":369,"libraryId":5,"type":218,"typeLabel":219,"stem":370,"options":371,"answer":30,"analysis":37},974234,"多线控制盘操作面板上设有多个手动控制单元，每个单元包括（ ），每个操作按钮均可控制具体设备的动作。",[372,374,376,378],{"key":20,"text":373,"correct":32},"一个操作按钮和启动、反馈两个状态指示灯",{"key":24,"text":375,"correct":32},"两个操作按钮和启动、故障两个状态指示灯",{"key":27,"text":377,"correct":32},"两个操作按钮和启动、反馈、故障三个状态指示灯",{"key":30,"text":379,"correct":22},"一个操作按钮和启动、反馈、故障三个状态指示灯",{"id":381,"libraryId":5,"type":218,"typeLabel":219,"stem":382,"options":383,"answer":27,"analysis":37},974235,"无遮挡的大空间或有特殊要求的房间，宜选择（ ）。",[384,386,388,390],{"key":20,"text":385,"correct":32},"缆式线型感温火灾探测器",{"key":24,"text":387,"correct":32},"线型光纤感温火灾探测器",{"key":27,"text":389,"correct":22},"线型光束感烟火灾探测器",{"key":30,"text":391,"correct":32},"线型定温火灾探测器",{"id":393,"libraryId":5,"type":218,"typeLabel":219,"stem":394,"options":395,"answer":24,"analysis":37},974236,"需要监测环境温度的地下空间等场所宜设置（ ）。",[396,397,398,399],{"key":20,"text":385,"correct":32},{"key":24,"text":387,"correct":22},{"key":27,"text":389,"correct":32},{"key":30,"text":391,"correct":32},{"id":401,"libraryId":5,"type":218,"typeLabel":219,"stem":402,"options":403,"answer":20,"analysis":37},974237,"电缆隧道、电缆竖井、电缆夹层、电缆桥架宜选择（ ）。",[404,405,406,407],{"key":20,"text":385,"correct":22},{"key":24,"text":387,"correct":32},{"key":27,"text":389,"correct":32},{"key":30,"text":391,"correct":32},{"id":409,"libraryId":5,"type":218,"typeLabel":219,"stem":410,"options":411,"answer":27,"analysis":37},974238,"在正常情况下有烟滞留的场所，不宜选择（ ）。",[412,413,414,415],{"key":20,"text":385,"correct":32},{"key":24,"text":387,"correct":32},{"key":27,"text":389,"correct":22},{"key":30,"text":391,"correct":32},{"id":417,"libraryId":5,"type":218,"typeLabel":219,"stem":418,"options":419,"answer":24,"analysis":37},974239,"线型光束感烟火灾探测器至侧墙水平距离不应大于（ ）m，且不应小于0.5m。",[420,422,424,426],{"key":20,"text":421,"correct":32},"5",{"key":24,"text":423,"correct":22},"7",{"key":27,"text":425,"correct":32},"10",{"key":30,"text":427,"correct":32},"15",{"id":429,"libraryId":5,"type":15,"typeLabel":16,"stem":430,"options":431,"answer":442,"analysis":37},974240,"在消防控制室图形显示装置（CRT）中，日志记录显示中可以查询到的信息是（ ）。",[432,434,436,438,440],{"key":20,"text":433,"correct":22},"用户名称",{"key":24,"text":435,"correct":22},"控制器地址",{"key":27,"text":437,"correct":32},"信息参数",{"key":30,"text":439,"correct":22},"信息内容",{"key":34,"text":441,"correct":22},"信息类型","ABDE",{"id":444,"libraryId":5,"type":15,"typeLabel":16,"stem":445,"options":446,"answer":97,"analysis":37},974241,"运行消防控制室图形显示装置软件，点击“查看”选项，有三个子菜单，分别为（ ）。",[447,449,451,453,455],{"key":20,"text":448,"correct":22},"报警历史记录查询",{"key":24,"text":450,"correct":22},"设备（设施）查询",{"key":27,"text":452,"correct":32},"火警历史记录查询",{"key":30,"text":454,"correct":32},"故障历史记录查询",{"key":34,"text":456,"correct":22},"操作和系统记录查询",{"id":458,"libraryId":5,"type":15,"typeLabel":16,"stem":459,"options":460,"answer":97,"analysis":37},974242,"下列关于总线控制盘的描述正确的是（ ）。",[461,463,465,467,469],{"key":20,"text":462,"correct":22},"火灾报警控制系统主要采用总线控制盘，其信号线由两根线组成，信号与供电共用一个总线，同时负责火灾探测器、手动火灾报警按钮和火灾声光警报器以及各类模块的通信和供电",{"key":24,"text":464,"correct":22},"总线控制盘的每一个按键对应一个总线控制模块，对消防设备的控制是由控制模块实现的",{"key":27,"text":466,"correct":32},"总线控制盘具有对每个受控消防设备进行自动控制的功能",{"key":30,"text":468,"correct":32},"一台集中火灾报警控制器（联动型）设置一个总线控制盘",{"key":34,"text":470,"correct":22},"总线控制盘为启动和停止受控消防设备提供了一种便捷的手动操作方式，可以代替烦琐的菜单操作",{"id":472,"libraryId":5,"type":15,"typeLabel":16,"stem":473,"options":474,"answer":485,"analysis":37},974243,"线型感温火灾探测器由敏感部件和与其相连接的信号处理单元及终端组成。敏感部件可分为（ ）。",[475,477,479,481,483],{"key":20,"text":476,"correct":22},"感温电缆",{"key":24,"text":478,"correct":22},"空气管",{"key":27,"text":480,"correct":22},"感温光纤",{"key":30,"text":482,"correct":22},"光纤光栅及其接续部件",{"key":34,"text":484,"correct":32},"线式感温元件及其接续部件","ABCD",{"id":487,"libraryId":5,"type":15,"typeLabel":16,"stem":488,"options":489,"answer":36,"analysis":37},974244,"线型感温火灾探测器按动作性能可分为（ ）。",[490,492,494,496,498],{"key":20,"text":491,"correct":22},"定温感温探测器",{"key":24,"text":493,"correct":22},"差温感温探测器",{"key":27,"text":495,"correct":22},"差定温感温探测器",{"key":30,"text":497,"correct":32},"可恢复式感温探测器",{"key":34,"text":499,"correct":32},"不可恢复式感温探测器",[501,504,507,510,513,516],{"id":218,"name":502,"category":7,"favorite":503},"领导干部任职前廉政法规知识测试题",92,{"id":505,"name":506,"category":7,"favorite":218},595,"建筑结构与设备",{"id":508,"name":509,"category":7,"favorite":218},715,"招标采购专业知识与法律法规",{"id":511,"name":512,"category":7,"favorite":218},848,"市政方向-通用基础",{"id":514,"name":515,"category":7,"favorite":8},534,"BIM工程师",{"id":517,"name":515,"category":7,"favorite":8},535]